What is the cross for a Belimo actuator NVF24SR used with a VB-9313-0-4-08 valve ?
Issue:
What actuator can be used to replace the NVF24SR actuator , when used with the obsoleted VB-9313-0-4-08 valve?
Product Line:
Valves and Actuators
Environment:
Maintenance
Cause:
Replacement
Resolution:
The Belimo actuator was 24 VAC , with 0-10V floating signal voltage , Spring Return, Stem up Normally Open actuator.
There are 2 options that can be used, the 1st would be using the MS41-7153 actuator, with AV-602-1 linkage kit .
The 2nd choice would be using a MS51-7103-100 actuator , which does not require a linkage kit to mount to the existing VB-9313 valve.
What actuator can be used to replace the NVF24SR actuator , when used with the obsoleted VB-9313-0-4-08 valve?
Product Line:
Valves and Actuators
Environment:
Maintenance
Cause:
Replacement
Resolution:
The Belimo actuator was 24 VAC , with 0-10V floating signal voltage , Spring Return, Stem up Normally Open actuator.
There are 2 options that can be used, the 1st would be using the MS41-7153 actuator, with AV-602-1 linkage kit .
The 2nd choice would be using a MS51-7103-100 actuator , which does not require a linkage kit to mount to the existing VB-9313 valve.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.