What are the S-flex enclosed drives minimum side by side spacing recommendations?
Resolution:
Mount each device so that the door can be opened at least 90°. The following are spacing recommendations:
• Mount all units with a minimum of 6.0 in. (152 mm) of space to the top and
bottom.
• Mount 1–40 hp 208/230 V and 1–60 hp 460 V units with a minimum of 3.5 in.
(89 mm) of space to the left and right.
• Mount 75–100 hp 460 V units with a minimum of 4.0 in. (102 mm) of space to
the left and right.
Please check the S-FLEX installation manual.
https://www.se.com/us/en/download/document/30072-451-83/