How Do I Wire a Speed Potentiometer to an Altivar Process Drive?
Resolution:
A speed potentiometer (speed pot) typically has three terminals:
- Center terminal (wiper): Connect to the desired analog input on the drive (AI1, AI2, or AI3). This terminal provides the speed reference signal.
- One outer terminal: Connect to the drive's +10 VDC supply.
- Other outer terminal: Connect to COM (common).
This wiring configuration allows the potentiometer to generate a variable analog signal that the Altivar Process drive uses as a speed reference.