How do I setup Clock synchronization between the HMISTU and a M221?

Issue:

How do I setup Clock synchronization between the HMISTU and a M221?

Product Line:

Clock synchronization between the HMISTU and a M221

Resolution:

In Vijeo Designer select the target properties and under Startup Options enable Time Management and set Type to PLC Dialog Table.

Please see attachment for more information.