How can we help you today?
SBO upgrade process failed (SBO 1.8.x to SBO 1.9.x)
Upgrade failed when upgrading Automation Server from SBO version 1.8.x to 1.9.x
Log indicates:
(Device Administrator | View | Last Upgrade Log)
ERROR: Exception encountered during database upgrade: StartUpMode UpgradeDatabase : RecoverableException: d:\dev\rb-rb-1.9.2-system\source\server\nsp_servers\csc\LonTypes\source\Lon2MapFileUtil.cpp(185) Invalid Data Error: Invalid_Data (0x10000) in module Impex(57). "Map data is too old for type: public.lon2.devicetemplates.pid90003A8200E90401. You need to run the Lon Repair command in the latest version of the workstation"
2019-04-10 07:14:02 INFORMATION: Database upgrade time: 5.28889 seconds
2019-04-10 07:14:02 INFORMATION: ============= End Configuration Database Upgrade =============
Source version: 1.8.1.79 Target Version: 1.9.2.45
Steps
1. Upgrade Workstation and Automation Server to the latest available version (SBO 1.8.1.3600)
2. Connect with Workstation to Automation Server
3. Select Server, and right-click Advanced | Repair LonWorks configuration ...
4. Select Next to repair when indicated "Server needs to be repaired"
5. Finally upgrade to Version 1.9 using Device Administrator
Log indicates:
(Device Administrator | View | Last Upgrade Log)
ERROR: Exception encountered during database upgrade: StartUpMode UpgradeDatabase : RecoverableException: d:\dev\rb-rb-1.9.2-system\source\server\nsp_servers\csc\LonTypes\source\Lon2MapFileUtil.cpp(185) Invalid Data Error: Invalid_Data (0x10000) in module Impex(57). "Map data is too old for type: public.lon2.devicetemplates.pid90003A8200E90401. You need to run the Lon Repair command in the latest version of the workstation"
2019-04-10 07:14:02 INFORMATION: Database upgrade time: 5.28889 seconds
2019-04-10 07:14:02 INFORMATION: ============= End Configuration Database Upgrade =============
Source version: 1.8.1.79 Target Version: 1.9.2.45
Steps
1. Upgrade Workstation and Automation Server to the latest available version (SBO 1.8.1.3600)
2. Connect with Workstation to Automation Server
3. Select Server, and right-click Advanced | Repair LonWorks configuration ...
4. Select Next to repair when indicated "Server needs to be repaired"
5. Finally upgrade to Version 1.9 using Device Administrator
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.