Are the analog inputs and outputs on the ATV660 electrically isolated?
Resolution:
No. The analog inputs and analog outputs are not electrically isolated.
If electrical isolation is required for the application, an appropriate external signal isolator or isolation module should be used between the ATV660 and the external control device.