Is there a wiring diagram for the ATV630 / ATV650 Process drives when supplied with single phase power?
There is no published document that includes a wiring diagram for single phase supply. Note that the power can be connected in any combination:
L1 / L2
L1 / L3
L2 / L3
Note that for single phase supply, the input phase loss feature needs to be disabled.
Complete settings - Error/Warning handling - Input phase loss = Ignore
PLEASE note that the approved use of ATV630/650 drives for single phase input to run 3 phase motors is very limited. See this knowledge article for detail: https://www.se.com/eg/en/faqs/FA279836/