How can we help you today?
What is the 70A and above branch breaker restriction for a NF 400A/600A MCB panel ?
Issue:
How many 70A and above breakers can be installed in a 400A NF Panel?
Product Line:
NF Panelboard
Environment:
Application
Cause:
Clarification
Resolution:
The maximum amount of 70A and above branch breakers allowed for the 400 Main breaker and Main lug NF panels, is Qty (8). Same goes with the 600A panel as 400A and 600A neutrals are the same. The only difference is the size of the incoming neutral lug. The restriction applies to both.
How many 70A and above breakers can be installed in a 400A NF Panel?
Product Line:
NF Panelboard
Environment:
Application
Cause:
Clarification
Resolution:
The maximum amount of 70A and above branch breakers allowed for the 400 Main breaker and Main lug NF panels, is Qty (8). Same goes with the 600A panel as 400A and 600A neutrals are the same. The only difference is the size of the incoming neutral lug. The restriction applies to both.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.