How to Compare and Print Settings Files
Issue
How to Compare and Print Settings Files
Product Line
MiCOM Relays
Environment
Easergy Studio
Cause
How to compare two settings file in Easergy Studio and print the results.
Resolution
Step 1: Expand a device in Studio Explorer and expand the Settings folder.
Step 2: Right-click on the first settings file and select ‘Compare – First File.’
Step 3: Right-click on the second settings file and select ‘Compare – Second File’
Step 4: Select ‘View Filers’ and ‘Columns’ for the comparison report
Step 5: Select rows to be included in the printed report
Step 6: Click on ’Print’ to print the setting files comparison report
Note: To compare settings files there must be at least two setting files in a system in Studio Explorer.
How to Compare and Print Settings Files
Product Line
MiCOM Relays
Environment
Easergy Studio
Cause
How to compare two settings file in Easergy Studio and print the results.
Resolution
Step 1: Expand a device in Studio Explorer and expand the Settings folder.
Step 2: Right-click on the first settings file and select ‘Compare – First File.’
Step 3: Right-click on the second settings file and select ‘Compare – Second File’
Step 4: Select ‘View Filers’ and ‘Columns’ for the comparison report
Step 5: Select rows to be included in the printed report
Step 6: Click on ’Print’ to print the setting files comparison report
Note: To compare settings files there must be at least two setting files in a system in Studio Explorer.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.