What should be done if Ethernet communication for M241/251 logic controllers is interrupted after several hours?
This may come from READ_VAR / WRITE_VAR / READ_WRITE_VAR function blocks being called with an unreachable Server IP address.
For example:
If controller the Ethernet interface settings are:
-
- Address: 192.168.0.50
- Subnet mask: 255.255.255.0
- Gateway: 0.0.0.0
and the READ_VAR function block tries to communicate with a Server at 192.168.10.20,
Then the Ethernet port may fail after several hours.
Workaround is :
- Stop trying to reach Server which are not in the same subnet as the controller.
- Check Ethernet cable status: ETH_R.i_wPortAIpStatus system variable value must be "DATA_EXCHANGE".
- Use a gateway address (use controller address itself if there is no relevant gateway on the network): requests to unreachable Server will be redirected to the gateway
Released for: Schneider Electric USA