How do I program and wire an E‑Stop for an ATV212 (Altivar 212) drive?
Resolution:
To safely integrate an emergency stop (E‑Stop) using a run permissive on the ATV212 drive, follow these steps:
1. Wiring
- Use a normally closed (NC) E‑Stop contact.
- Connect the contact between terminals R and P24.
- This ensures the circuit opens when the E‑Stop is pressed.
2. Programming
- Set parameter F110 = 0 (assigns the input function).
- Set parameter F112 = 1 (enables run permissive logic).
3. Operation
- When the E‑Stop is activated (contact opens), the drive:
- Removes output power to the motor
- Displays “OFF”, indicating the run permissive is not active
- Normal operation resumes only when the circuit is restored.
Tip: Using a run permissive ensures the motor stops immediately when the safety circuit is interrupted.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.