How can the BMEP58_ECPU_EXT.NETWORK_HEALTH DDT be reset?

Issue
After correcting a network topology or broadcast storm issue on my M580, the Device DDT variable structure (of DDT Data Type = T_BMEP58_ECPU or T_BMEP58_ECPU_EXT) reports that a potential network broadcast storm is detected.

e.g.) BMEP58_ECPU_EXT.NETWORK_HEALTH (Bit 8 starting from 0 in the ETH_STATUS Word)  = 0
which indicates that a potential network broadcast storm is detected.
The value is not reset back to 1 (which means that a network broadcast storm is not detected)

Product line
EcoStruxure Control Expert, Unity Pro, Modicon M580 PLC

Resolution
Before firmware version 2.80 for M580 PLCs, a power cycle of the CPU was required to reset the bit. From V2.80 forward, the bit will reset itself after the problem is corrected.

A firmware upgrade >=2.80 is recommended to correct the behavior.


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.