How can we help you today?
Can an Ethernet module be added to a "Non-E" version of an ATV340 series drive?
Issue:
Customer has purchased a "non-E" version of the ATV340 drive but needs to communicate with the drive via Ethernet.
Product Line:
Altivar Machines, Altivar 340
Environment:
"Non-E" version of the drive (last digit of part number is NOT an E)
Cause:
Clarification of product capabilities.
Resolution:
No. An ATV340 drive that does not have integrate Ethernet communication options can not have them added via an option card. There are two versions of the ATV340 series drive, the E and the Non-E. If Ethernet communication is needed you must purchase the E version (Last digit of part number is E).
Customer has purchased a "non-E" version of the ATV340 drive but needs to communicate with the drive via Ethernet.
Product Line:
Altivar Machines, Altivar 340
Environment:
"Non-E" version of the drive (last digit of part number is NOT an E)
Cause:
Clarification of product capabilities.
Resolution:
No. An ATV340 drive that does not have integrate Ethernet communication options can not have them added via an option card. There are two versions of the ATV340 series drive, the E and the Non-E. If Ethernet communication is needed you must purchase the E version (Last digit of part number is E).
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.