Can the Premium X-Bus cables be used for the X80 expansion racks?

Issue
Migrating from Premium to M580 and the current installation has X-Bus cables running through bus ducts connecting the Premium racks. Can these cables be used for the expanded X80 racks or must new cables be used?

Product line
Modicon M580, TSX Premium

Resolution
The Premium X-Bus cables can be left in place and connected to the BMXXBE0800 expansion modules. There is no need to run new expansion cables during this migration. The X-Bus terminators that are in place in the Premium racks can also be saved as spares for the BMXXBE0800 modules.