Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How can I change the relay status from NO to NC on the Altivar Process Drives?
Issue:
They need to change the function of the output relay from Normally Open contact to a Normally Closed contact.

Product line:
Altivar Process, ATV600 ATV900

Environment:
all

Cause:
The Altivar Process drives come with only R1 having a normally open and normally closed contact.  R2, R3 and the extended IO Card relays are all Normally Open only.

Resolution:
Under the Relay configuration menu (i.e. R2 Configuration > go to R2 Active at.  The factory setting is 1 (closed).  Change this value to 0 for active when open to invert the relay output signal.

NOTE:  Operating State Fault (FLT) cannot be assigned to 0.  If an additional NC contact is needed for Fault indication, add an external control relay with the additional contacts.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings