How can we help you today?

Magelis shows error "configuration file is not unicode"

Issue:
The Magelis HMI fails to boot properly and there is an application halt. The error on the dialog states the following:

Config problem:the configuration file is not unicode
KAOScore:PortableProjectConfiguration.cpp:line 406


Product Line:
Magelis HMI programmed Vijeo Designer (any version)

Resolution:
This error is a result of a corrupt Vijeo Designer installation on the PC where the software is installed. To resolve this issue, please re-install Vijeo Designer and re-download to the HMI.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.