How can we help you today?
How to setup VIA and VIB on the ATV212 drive using 0-5V instead of 0-10V?
Issue:
Can I set 0-5V analog signal on VIA and VIB on the ATV212 drive?
Product Line:
Altivar Machines, Altivar 212, S-Flex
Environment:
All model numbers, all serial numbers
Cause:
Customer wanted to use 0-5V instead of 0-10V.
Resolution:
For setting up VIA using 0-5V, then follow the steps below:
F201 = 0
F202 = 0
F203 = 50% or 5V
F204 = 60 for 60Hz in US
For setting up VIB using 0-5V, then follow the steps below:
F210 = 0
F211 = 0
F212 = 50% or 5V
F213 = 60 for 60Hz in US
In addition, please make sure SW100 (voltage/current selection for analog I/O VIA and VIB) are set for U (voltage).
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.