How can we help you today?
Can the Altistart 48 use Fast acting fuses on the line power?
Issue:
Fact acting fuses protecting the ATS48
Product line:
Altistart 48 softstart controller
Environment:
all
Cause:
Documentation does not show fact acting
Resolution:
Fast acting fuses are not recommended. The starting currents on a soft start can be upwards of 400% or more of motor FLA for the duration of the ramp to full speed. It is recommended to use time delay fuses only.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.