How can a project be cleared from an M340?
Issue
Attempting to load a program to an M340 that is password protected with a forgotten password.
Product line
Modicon M340, Unity Pro, Control Expert
Resolution
Power down, remove SD card and power up. Transfer the new program to the M340 then insert the SD card under power and update it with the new just transferred program.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Attempting to load a program to an M340 that is password protected with a forgotten password.
Product line
Modicon M340, Unity Pro, Control Expert
Resolution
Power down, remove SD card and power up. Transfer the new program to the M340 then insert the SD card under power and update it with the new just transferred program.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.