Can a RIM module be used for ZSI between Micrologic Series B circuit breakers and Masterpact MTZ?

Product Line:
Circuit Breakers

Resolution:
The newer RIM, LV848892SP, can be used with MTZ, NW, and Powerpact P and R frame breakers without restriction.
It can also be used with Series B (SE, NE, PE) as main breakers, but NOT with Series B downstream (feeder/branch). For these, use the obsolete S48890 RIM.