What Modbus TCP Unit ID can be used to communicate to BMENOC030x cards?

Issue
In the past, using a Unit ID of 255 has been a problem on some products communicating over Modbus TCP.

Product line
Modicon X80, Modicon M580

Resolution
Function code 3 with a Unit ID of 255 will return diagnostic information for the Quantum and M340 NOC products.
Function code 3 with a Unit ID of 100 will return diagnostic information for the M580 NOC products.
Those are the only Unit ID's that will return something other than register information when used in conjunction with the Function code 3. We are not aware of any other restrictions.



If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.