What can cause a CrF1 (Precharge Fault) on an ATV930 when a Bonitron unit or another external power supply is used to power the DC bus?
When the ATV930 is powered from an external DC bus source, the drive must be configured so it does not expect to use its internal precharge circuit.
- Go to Menu 8: My Preferences and set Access Level to Expert.
- Navigate to Menu 5: Complete Settings > Generic Functions > Bus Ref Link > DC Bus Source Type.
- Set DC Bus Source Type to Drive with REC (MCPE).
This setting configures the ATV930 for operation with the external DC bus supply instead of its internal precharge circuit.