How can we help you today?
At what DC voltage level does the Brake resistor engage in the ATV900 drives?
Issue:
VDC level where the brake resistor is turned on.
Product line:
Altivar Machines, Altivar 900 series
Environment:
All model and serial numbers
Cause:
Determine adjustments for roller miller or other high inertia applications
Resolution:
The resistor will engage at 780VDC on the DC bus. This setpoint is adjustable using the VBR parameter (Brake Level) listed under the Motor Control Menu.
Factory setting for VBR is 780V
VDC level where the brake resistor is turned on.
Product line:
Altivar Machines, Altivar 900 series
Environment:
All model and serial numbers
Cause:
Determine adjustments for roller miller or other high inertia applications
Resolution:
The resistor will engage at 780VDC on the DC bus. This setpoint is adjustable using the VBR parameter (Brake Level) listed under the Motor Control Menu.
Factory setting for VBR is 780V
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.