Why is ramp stop the only option for the Type of Stop (Stt) on the ATV320 drive?
Issue:
On ATV320 drive, only ramp stop can be assigned to Type of Stop (Stt).
Product line:
ATV320
Environment:
All serial numbers
Cause:
Customer wanted to assign Freewheel Stop.
Resolution:
If the brake logic function (bLC) has been enabled or if Low speed time out (tLS) is not 0, then the Type of Stop (Stt) parameter is forced to Ramp Stop..