Contact Resistance Testing and Circuit Breaker Performance

Issue:
Contact resistance testing

Product Line:

Circuit Breakers

Resolution:

While contact resistance testing is intended to be a predictor of breaker thermal performance in service, it is not a design specification and new-breaker contact resistance is subject to wide variation due to factors such as resistive oxidation from the manufacturing process and environmental factors after manufacturing.  The arbitrary standards suggested by NETA and other testing procedures result in many false negatives and should not be relied upon as the sole predictor of breaker thermal performance.

For customers who want to do contact resistance testing, we recommend accepting the breakers that are within the limits acceptable to the customer on the first pass, and for those breakers that are outside those limits on the first pass we recommend referring to the linked product data bulletin (also attached) for further direction. https://download.schneider-electric.com/files?p_enDocType=Data+Bulletin&p_File_Name=0600DB1901.pdf&p_Doc_Ref=0600DB1901

Schneider Electric USA

Attachment(s)
Contact Resistance 0600DB1901.pdf [212.67 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings