How can we help you today?

How to perform a factory reset on the Altivar ATV320 drive?

Article available in these languages:

Issue:
How can I perform a Factory Reset on the ATV320 drive.

Product Line:
Altivar 320

Resolution:
To perform a factory reset from power up:
Enter on dial
Scroll to CONF menu and enter
Scroll to FCS- and enter
Scroll to FRY- and enter
Select All so that " mark is at top instead of bottom
Now go to GFS parameter
Set it to YES and hold enter for 2 seconds until display LEDs stop flashing
VFD is reset to factory defaults

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.