What Class of fuse does the CD221N, CD321N and CD321NRB general duty safety switches accept?
Issue:
Product design features
Product Line:
General Duty Safety Switches
Environment:
Fuses
Cause:
Installation
Resolution:
These switches accept Class H or K fuses as standard. For design Series E1, E2 or E3, options include Class R fuses (field install Class R Fuse Kit DRK30). With Class H or K fuses installed, the switch is rated for use on systems with up to 10,000 RMS Symmetrical Amperes available fault current. With Class R fuses (and DRK30 fuse kit installed) the switch is rated for use on systems with up to 100,000 RMS Symmetrical Amperes available fault current.
NOTE: DO NOT USE RENEWABLE LINK FUSES IN SQUARE D SAFETY SWITCHES. The use of renewable link fuses may adversely affect user safety, impair reliability and will void the warranty.
Product design features
Product Line:
General Duty Safety Switches
Environment:
Fuses
Cause:
Installation
Resolution:
These switches accept Class H or K fuses as standard. For design Series E1, E2 or E3, options include Class R fuses (field install Class R Fuse Kit DRK30). With Class H or K fuses installed, the switch is rated for use on systems with up to 10,000 RMS Symmetrical Amperes available fault current. With Class R fuses (and DRK30 fuse kit installed) the switch is rated for use on systems with up to 100,000 RMS Symmetrical Amperes available fault current.
NOTE: DO NOT USE RENEWABLE LINK FUSES IN SQUARE D SAFETY SWITCHES. The use of renewable link fuses may adversely affect user safety, impair reliability and will void the warranty.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.