Where can I find the pinout for modbus cable part number VW3A8306R03?
Resolution:
The VW3A8306R03 cable uses the following pins for Modbus communication:
- Pins 4 and 5: Twisted data pair. Pin 4 is D1 (DB / Data +) and Pin 5 is D0 (DA / Data −).
- Pin 8: 0 V / common.
Refer to the attached document for the complete wiring diagram and additional connection details.