How can we help you today?
What are the default IP addresses on the M241/M251 controllers?
Depending on the Software and Firmware version, the default IP addresses are:
With SoMachine and Machine Expert V1.1:
- M241 Embedded Ethernet: 10.10.x.x
- M241 TM4ES4: 11.11.x.x
- M251 Eth1: 11.11.x.x
- M251 Eth2: 10.10.x.x
The default subnet mask is Default Class A Subnet Mask of 255.0.0.0.
From Machine Expert V1.2:
- M241 Embedded Ethernet: 10.10.x.x
- M241 TM4ES4: 10.11.x.x
- M251 Eth1: 10.11.x.x
- M251 Eth2: 10.10.x.x
The default subnet mask is Default Class B Subnet Mask of 255.255.0.0.
The last 2 fields in the default IP address are composed of the decimal equivalent of the last 2 hexadecimal bytes of the MAC address of the port.
The MAC address of the port can be retrieved on the label placed on the front side of the controller.
NOTE: A MAC address is always written in hexadecimal format and an IP address in decimal format. Convert the MAC address to decimal format.
Example: If the MAC address is 00.80.F4.01.80.F2, the default IP address is x.x.128.242.
NOTE: To take into account the new IP address after the download of a project, reboot the controller by doing a power cycle.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.