How can we help you today?

ATV320 How do you change the R2 relay to a Normally Closed contact

Issue:
ATV320  How many relay contacts?

Product Line:
Altivar Machine, ATV320

Environment:
All serial numbers

Resolution:
There are 2 sets of  contacts.

R2A - R2C  normally open
NO contact of programmable relay R2

R1A  1 normally open 1 normally closed
R1A NO contact of relay R1
R1B NC contact of relay R1
R1C Common point contact of relay R1

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings