How can we help you today?
Word order for RealFLO Modbus Registers in an x70 Controller
RealFLO Modbus registers require a word order of “High byte/High word first”. When running a RealFLO flow computer in a SCADAPack x70 controller, the user must ensure that this is set correctly.
The following screen shots (from Remote Connect) show the proper settings for setting the RealFLO Modbus Registers word order.
1. Ensure that the ‘Realflo Flow Computer’ box is checked in the ‘Project Settings’ dialog
2. Ensure that the word order is set properly in the Modbus | Master/Client | FlowComputer dialog. The correct setting is 'High byte/High word first'.
3. Ensure the word order is set properly in the Modus | SlaveServer dialog. The correct setting is 'High byte/High word first'.
With the above settings in place, the modbus registers that contain the flow computer data will display the data correctly.
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.