What are the differences between HCJ and HCM interiors?

Article available in these languages: Spanish

Issue:
Differences on the HCJ and HCM I-Line interiors

Product Line:
I-Line

Environment:
Panelboards

Resolution:
The HCJ is an update provided for the HCM Interior frame. Listed below are the updates we have on HCJ I-Line Interiors:

1. All deadfront openings on HCJ interiors are enlarged/widened to allow acces on electronic trip units of Powerpact H/J/L Frame breakers that use Micrologic 3/5/6 trip units.
2. While the width of HCJ and HCM interiors and enclosures are the same, the options for HCJ enclosures are limited to 3 options (48", 73" and 91" high).The 64" option was removed to provide more uniformity in the selection of boxes.
3. HCJ enclosures are 9.5" deep compared while HCM enclosures are all 8" deep. This is to standardize the depth to other I-Line Panelboards and all options in HCJ interiors.
4. HCJ Nema 3R and SS Enclosures are all 9.5" deep to conform with the update on number 3.
5. MLO and Main Breaker options for HCJ begin with 400A instead of the HCM's 225A.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings