How do you set up ramp switching on an ATV340 drive?

Resolution:

Ramp switching allows the drive to alternate between two sets of acceleration and deceleration times based on:

  • A digital input or communication signal, or
  • A frequency threshold
  1. Set the primary ramps
    Under Simply Start:
    1. ACC → Acceleration time (Ramp 1)
    2. DEC → Deceleration time (Ramp 1)
  2. Configure ramp switching
    Go to: Complete Settings → Generic Functions → Ramp Switching
    1. RPS (Ramp Switching Assignment): Assign a logic input (LI1–LI6) or communication control to activate Ramp 2
  3. Set the secondary ramps
    1. AC2 → Acceleration time (Ramp 2)
    2. DE2 → Deceleration time (Ramp 2)
    3. When the RPS input is active, the drive uses AC2 / DE2.  When inactive, it returns to ACC / DEC
  4. (Optional) Use frequency-based switching
    1. FRT (Ramp Threshold Frequency)
      1. If set > 0 Hz:
        • Below FRT → ACC / DEC (Ramp 1)
        • Above FRT → AC2 / DE2 (Ramp 2)
If RPS (logic input) is active, it overrides the FRT setting. The drive will use Ramp 2, regardless of motor speed.

Use:

  • RPS for external control (e.g., process signals)
  • FRT for automatic switching based on speed

Test the configuration to ensure smooth transitions between ramps.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.