What is the minimum and maximum Current Limit (ILt) setting available on the ATS48 Altistart soft starter?
Resolution
The Current Limit (ILt) parameter on the ATS48 is adjustable from 150% to 700% of the motor nominal current (In) setting.
However, the maximum output current is limited to 500% of the ATS48 soft starter rated current. Therefore, even if ILt is configured up to 700%, the actual current cannot exceed five times the soft starter's rated current