What is the difference between iEM3455 and iEM3455C1/C2 models?
Issue
Value of CT primary cannot be changed in iEM3455C1 and iEM3455C2 models
Product line
Powerlogic Meter iEM3000 series
Environment
Front panel
ION Setup 3.2
Resolution
The difference between the models iEM3455, iEM3455C1 and iEM3455C2 are that of CT primary configuration. For iEM3455, CT primary can be changed to any LVCT but the value in iEM3455C1 and iEM3455C2 is fixed to 100 amps and 200 amps respectively, this cannot be modified.
iEM3000 series documentation can be found at the following link FA352325