How do you install communicating MX and XF coils on a Masterpact MTZ breaker?

Issue:
Installation of communicating coils on MTZ

Product Line:
Circuit Breakers

Resolution:
Isolation module LV850056SP is required.
The isolation module comes with three wire harnesses, which are needed for connecting the coils to the control unit. If these become lost or damaged, they can be replaced with catalog number LV833118SP for MTZ1 or LV847904SP for MTZ2 and 3.
You will also need secondary wiring terminal block LV847074SP for a fixed breaker or LV847849SP for a drawout (one per coil).

See catalog pages and instruction bulletins attached.