Is there any automated way to modify the parameter Sensor Alignment of the module BMXAMI0810?
Issue
Fill the field Alignment automatically
Product Line
M580
Environment
Control Expert
Resolution
Control Expert has DFB's that you can write/read parameters
Adjustment Parameter limitation
In M580 RIO, adjustment parameters cannot be changed from the PLC application during operation (no support of READ_PARAM, WRITE_PARAM, SAVE_PARAM, RESTORE_PARAM).
Fill the field Alignment automatically
Product Line
M580
Environment
Control Expert
Resolution
Control Expert has DFB's that you can write/read parameters
| I/O Module Location | I/O Vision | Function Block |
| Local Rack | Topological addressing/IODDT | READ_PARAM, WRITE_PARAM |
| DeviceDDT | READ_PARAM_MX, WRITE_PARAM_MX |
Adjustment Parameter limitation
In M580 RIO, adjustment parameters cannot be changed from the PLC application during operation (no support of READ_PARAM, WRITE_PARAM, SAVE_PARAM, RESTORE_PARAM).