How to set PID preset references for the ATV630 drive?
Issue:
Can I program drive to switch between different set points on PID controller for the ATV630 drive?
Product Line:
ATV630
Environment:
All models, all serial numbers
Cause:
Customer wanted to easily switch between three set points, 40, 60 and 80 PSI.
Resolution:
Under the main menu, enter complete setting -> Pump Functions -> PID Controller -> PID Reference -> PID preset references:
Assign a digital input (DI5) for 2 PID Preset Assign
Enter 40PSI for RefPID Preset 2
Assign a digital input (DI6) for 4 PID Preset Assign
Enter 60PSI for RefPID Preset 3
Enter 80PSI for RefPID Preset 4
Note: This function can be accessed if [PID feedback ass.] PIF is assigned.
Can I program drive to switch between different set points on PID controller for the ATV630 drive?
Product Line:
ATV630
Environment:
All models, all serial numbers
Cause:
Customer wanted to easily switch between three set points, 40, 60 and 80 PSI.
Resolution:
Under the main menu, enter complete setting -> Pump Functions -> PID Controller -> PID Reference -> PID preset references:
Assign a digital input (DI5) for 2 PID Preset Assign
Enter 40PSI for RefPID Preset 2
Assign a digital input (DI6) for 4 PID Preset Assign
Enter 60PSI for RefPID Preset 3
Enter 80PSI for RefPID Preset 4
Note: This function can be accessed if [PID feedback ass.] PIF is assigned.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.