How can we help you today?

How can you turn ERMS Maintenance Mode OFF on an MTZ breaker if turned on via a switch, but the switch is not installed?

Issue:
How to turn ERMS to OFF without a switch.  How to disable ERMS on Masterpact MTZ with ESM Module installed.  This procedure may be helpful when removing the breaker from the cell for primary or secondary injection testing. See attachments.

Product Line:
Circuit Breakers

Resolution:

  1. Apply 24 Vdc to the ULP port F1-/F2+ terminals, using a USB cable to turn ON the control unit will not energize the ESM module.
  2. Apply 24Vdc to the ESM terminals 484(+)/471(-) to disengage ERMS (otherwise it will stay engaged even when step 2 is done)
  3. Using EPC, go into accessory declarations and turn off ESM. (Un-declare the ESM in the control unit)

This process will disable the ERMS function in the control unit.

See attachment for ESM wiring diagram and detailed wiring instructions.

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.