How to script a multi-condition IF/ELSE statement in EcoStruxure Operator Terminal Expert
Issue:
Looking for an example on how to script an IF/ELSE statement in Blockly script in EcoStruxure Operator Terminal Expert
Product Line:
EcoStruxure Operator Terminal Expert (formerly known as Vijeo XD)
Resolution:
Take for example that we need to script the following block of code in Blockly script in EcoStruxure Operator Terminal Expert:
/**********************************************/
if((Var1==1) || (Var2==2) || (Var3==3))
{
Var4 = 1
}
else
{ Var4 = 0
}
/*********************************************/
We can make use of the following items in EcoStruxure Operator Terminal's Blockly script to establish the same multi-conditon IF/ELSE statement:
1) First we start with an Orange Trigger Block. For our example, I have chosen the Periodic - When - Do block. This will run every 100 ms.
2) The next block is the Purple If/Do/Else Block.
3) For the Logical "OR" of the 3 conditions, we need to snap two Blue Logicial Conditon Blocks together. If you had more conditions, you would use more of the same blocks.
4) Going deeper into the Logical Condition Blocks, we need to establish our comparison blocks. For this, we will three Blue Comparison Blocks. Note that these blocks need the blue Variable and Constant blocks as well. The Variable block is used to define the HMI variable and the Constant block is used to define the value to compare the HMI variable to.
5) Finally, we need to make our Do/Else operations. For these, we will use the Bronze Value Change blocks. Again, this block will need the blue Variable and Constant blocks as well. Remember to set the appropriate value to set Var4 to for the Do and Else conditions.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.