How can we help you today?
Why does the BMENOP0300 module show an invalid configuration despite a successful validation of its IEC61850 Configuration Tool (IEDCT) ?
Issue:
Why the BMENOP0300 module show invalid configuration and the Modicon IEC61850 configuration tool validation is Pass with no errors?
Product Line:
Modicon M580 Controller, BMENOP0300, NOP
Environment:
All
Resolution:
The BMENOP0300 module requires the Data Dictionary (Mandatory) as PLC embedded data.
Ensure that the “Only HMI Variable” option is not selected in the project settings. If it is selected, verify that the module device DDT variable has the “Only HMI” option enabled to guarantee that these variables are embedded in the CPU:
Released for: Schneider Electric USA
Explore more
Product:
Explore more
Product:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.