Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What does backfed mean in conjunction with a circuit breaker and how is this installed?

Article available in these languages: Spanish

Issue:
Backfeeding Application

Product Line:
Panelboards

Environment:
UL 67, UL 50, CSA C22.2 No.'s 20-M1989 & 94-M91, NEMA PB1, NFPA 70 Art. 408, Federal Specification W-P-115C Type 1 Class 1 , 2003 IBC, NFPA 5000, ASCE/SE17


Cause:
Unfamiliarity with specialised terminology.

Resolution:
In a panelboard application, a back-fed main breaker is mounted on the branch bus, occupying normal branch breaker mounting space or circuits, instead of in the separate, vertical position more typical of a main breaker. The normal load-side lugs of the back-fed main circuit breaker actually become the (incoming) line lugs of the panelboard, and power flows to the panelboard bussing through the branch connectors of the panelboard interior, to which the back-fed main breaker is connected.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings