My Transformer is very noisy. Can anything be done to quiet the sound level?

Article available in these languages:

Issue:
Transformer sound levels

Product Line:
LV Transformers

Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric

Resolution:
Low Voltage Ventilated and Non Ventilated Transformer Installers should be sure to fully loosen the core and coil mounting nuts in each corner of the Transformer assembly to allow the rubber sound/vibration dampening pads to work properly.
(Refer to page 25 of the attached bulletin).

Transformers are allowed, by NEMA standards, a certain amount of normal operating sound level which varies with kVA size. If you think your Transformer exceeds these allowable limits then contact your local Schneider Electric Distributor.  There is no dependable or safe way to reduce the actual sound level of the transformer at the job site. However, sound can be amplified by reflecting hard surfaces near Transformers. Acoustical treatment of these surfaces, or reorientation of the Transformer can sometimes reduce objectionable noise. Schneider Electric can offer an engineered, reduced sound level Transformers on a special order basis. Contact your local Distributor for more information.

Schneider Electric USA

Attachment(s)

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.