Three-phase Transformers in the Schneider Electric catalog have Delta connected primaries. What if I have a Wye connected service?
Issue:
Delta connected primaries on three phase Transformers
Product Line:
LV Transformers
Environment:
Applies to three phase Transformers by SquareD/Schneider Electric
Resolution:
Delta connected primaries are perfectly suitable for use on Wye services. The contractor uses the 3 phases and ground from the service into the Transformer and does not include the neutral wire. The reason that Wye primaries are not normally recommended is that Wye-Wye and Wye-Delta Transformers have special application issues that must be observed to avoid serious problems. As a result, they are seldom used in the electrical industry. For further information contact your distributor or local SquareD/Schneider Electric sales office.
Delta connected primaries on three phase Transformers
Product Line:
LV Transformers
Environment:
Applies to three phase Transformers by SquareD/Schneider Electric
Resolution:
Delta connected primaries are perfectly suitable for use on Wye services. The contractor uses the 3 phases and ground from the service into the Transformer and does not include the neutral wire. The reason that Wye primaries are not normally recommended is that Wye-Wye and Wye-Delta Transformers have special application issues that must be observed to avoid serious problems. As a result, they are seldom used in the electrical industry. For further information contact your distributor or local SquareD/Schneider Electric sales office.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.