Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How many ON-OFF operations can a circuit breaker withstand?
Issue:
How many ON-OFF operations can a circuit breaker withstand?

Product Line:
Square D, Powerpact, Masterpact

Resolution:
This table lists the UL endurance test requirements for different frame sizes:
Frame Size (A)Full Load OperationsNo Load Operations
0-100 6,000 4,000
101-225 4,000 4,000
226-600 1,000 5,000
601-800 500 3,000
801-2500 500 2,000
2501-4000 400 1,100

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings