How can we help you today?

What branch connector is required to replace a Q1B circuit breaker with a QOB circuit breaker in an NQOB panelboard?

SK5668 is the bus finger or panelboard connector kit for use when replacing a Q1B branch in an NQOB panel. The kit will accept QOB breakers. This is a 3 pole kit with A, B, and C phase connectors. In a 225 amp NQOB interior, this kit will allow you to mount 6 poles of breakers whether they are 1 pole, 2 pole, or 3 pole breakers. In a 400/600 amp NQOB interior, this kit will allow you to mount 3 poles of breakers whether they are 1 pole, 2 pole, or 3 pole breakers.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings