What does suffix 35 indicate on a circuit breaker?

Issue:​
Meaning of suffix 35 on a circuit breaker.

Product Line:
Molded Case Circuit Breaker

Resolution:
Suffix 35 indicates that the breaker is factory calibrated for a 50°C ambient temperature instead of the standard 40°C. Breakers with suffix 35 are not UL listed.
This suffix does not apply to Multi-9, Powerpact, Masterpact breakers, or legacy breakers with Micrologic trip units.