Issue:
What voltage drop is required for a UVR to trip a breaker?
Product Line:
Circuit Breakers
Resolution:
The UVR is guaranteed to let the breaker hold above 70% Vn and is guaranteed to trip the breaker below 35% Vn. The trip point would be somewhere between 35 and 70% Vn.
What voltage drop is required for a UVR to trip a breaker?
Product Line:
Circuit Breakers
Resolution:
The UVR is guaranteed to let the breaker hold above 70% Vn and is guaranteed to trip the breaker below 35% Vn. The trip point would be somewhere between 35 and 70% Vn.
Released for:Schneider Electric USA