Product Line:
G shunt trip
Environment:
Electrical distribution
Resolution:
No. Applying voltage to the G shunt trip will also apply voltage to the unprotected GFM output and will damage the GFM. Also, the G shunt trip has no coil clearing switch and will burn out on a longer than momentary contact.
G shunt trip