Which wire sizes will terminate in the AL400LA lug for the LA, LH, and Q4 circuit breakers?
Product Line:
LA, LH, and Q4
Environment:
Electrical Distribution
Resolution:
(1) #1 AWG - 600 kcmil (50-300 mm²) or (2) #1 AWG - 250 kcmil (50-120 mm²) aluminum or copper conductors.
LA, LH, and Q4
Environment:
Electrical Distribution
Resolution:
(1) #1 AWG - 600 kcmil (50-300 mm²) or (2) #1 AWG - 250 kcmil (50-120 mm²) aluminum or copper conductors.
Released for: Schneider Electric USA